ISO 9001CEEuroventEN 1886 Designed & manufactured in İzmir, Türkiye

Language
info@technogen-hvac.com +90 532 201 00 11 Request a quote

Techno-Pool

Dehumidification and climate control for indoor swimming pools.

Technogen Techno-Pool — Pool Air Handling Units
  • 0models
  • 64–505m²pool surface area
  • 0kg/hmax. dehumidification
  • 0m³/hmax. airflow

01Overview

Crystal-clear comfort
above the water.

Techno-Pool units deliver reliable humidity control, stable climate regulation and high energy efficiency for indoor pools — from hotels and spa centres to municipal facilities and luxury residences.

Every unit is equipped with heat recovery, durable construction and smart automation for long-term savings in operating costs.

Heat recovery

Heat recovery as standard

All units are equipped with heat recovery systems that enhance energy efficiency.

R407C

Scroll compressors

R407C refrigerant with scroll compressors in single or dual circuits.

3 options

Fan choice

Belt-driven, plug fan or EC plug fan options.

G4 → F9

Filtration

Standard G4 panel filter with optional M5–F9 bag filters.

Pool-proof

Corrosion-ready build

50 mm rock-wool insulation, epoxy-coated coils and a stainless-steel drainage system.

200 m

Smart automation

Humidity and temperature sensors, frequency converters, scheduling and remote control up to 200 m.

02Range

Eight models.
Every pool size.

Techno-Pool covers pool surface areas from 64 to 505 m² — selected to the hall, the water and the people using it.

Pool surface area64 – 505 m²
0600
Dehumidification capacity18.6 – 150.5 kg/h
0175
Airflow≈ 1,972–15,009 CFM3,350 – 25,500 m³/h
030,000
Heating capacityUp to 266.5 kW
0300
Cooling capacityUp to 2 × 82.7 kW
0200

Ranges across the eight Techno-Pool models. Per-model data is in the technical catalogue.

03Specifications

Technical overview.

Models
8
Pool surface area
64 – 505 m²
Dehumidification
18.6 – 150.5 kg/h
Airflow
3,350 – 25,500 m³/h (≈ 1,970–15,010 CFM)
Cooling capacity
Up to 2 × 82.7 kW
Heating capacity
Up to 266.5 kW
Fans
Belt-driven, plug fan or EC plug fan
Refrigerant
R407C, scroll compressor (single or dual circuit)
Filtration
G4 panel filter standard; optional M5–F9 bag filters
Construction
50 mm rock-wool insulation, epoxy-coated coils, stainless-steel drainage
Automation
Humidity and temperature sensors, frequency converters, programmable scheduling, remote control up to 200 m
Applications
Hotels, spa centres, municipal facilities, luxury residences

04Model data

Catalogue figures,
at a glance.

As published in the Techno-Pool technical catalogue.

m²

A first guide from the catalogue figures. Our engineers confirm the selection for your project.

ModelPool surfacem²Dehumidificationkg/hAirflowm³/hCooling capacitykWHeating capacitykWCompressor circuitsTotal powerkWDimensions (L × W × H)mmWeightkg
TP-336418.63,35021.137.4110.044,725 × 915 × 1,5841,350
TP-458926.54,50030.749.6114.324,775 × 915 × 1,8901,500
TP-6512235.66,50040.264.1118.324,878 × 1,221 × 1,8901,700
TP-8416547.78,40054.584.3124.84,997 × 1,374 × 2,1962,000
TP-12524574.212,50083129.3134.65,053 × 1,833 × 2,1962,500
TP-15530699.215,500110.4159.3255.65,781 × 1,833 × 2,0522,900
TP-215425127.721,50072.1 × 2229.7280.126,017 × 2,292 × 2,8083,850
TP-255505150.525,50082.7 × 2266.5280.126,538 × 2,292 × 3,1144,800

Full model codes end in -PHR-APF-NR-WH (e.g. TP-33-PHR-APF-NR-WH). Scroll compressors, R407C. Two plug fans, 350 Pa external pressure on return and supply, G4/G4 filters, fan motors 3P/380 V/50 Hz. Two-circuit models show cooling capacity per circuit (× 2). The catalogue does not state rating conditions for the capacities.

Download catalogue →

Specify Techno-Pool for
your next project.

Share your drawings or requirements and our engineering team will come back with a tailored Techno-Pool selection.