Heat recovery as standard
All units are equipped with heat recovery systems that enhance energy efficiency.
Dehumidification and climate control for indoor swimming pools.
01Overview
Techno-Pool units control humidity and temperature in indoor pool halls: hotels, spa centres, municipal pools and private residences. Each unit is selected from the evaporation load, which VDI 2089 Part 1 calculates from the water area, the water and air temperatures and how the pool is used.
Every unit has heat recovery and a factory-mounted control panel, so it is ready to run when it arrives on site.
All units are equipped with heat recovery systems that enhance energy efficiency.
R407C refrigerant with scroll compressors in single or dual circuits.
Belt-driven, plug fan or EC plug fan options.
Standard G4 panel filter with optional M5–F9 bag filters.
50 mm rock-wool insulation, epoxy-coated coils and a stainless-steel drainage system.
Humidity and temperature sensors, frequency converters, scheduling and remote control up to 200 m.
02Range
Techno-Pool covers pool surface areas from 64 to 505 m². Choose the model by evaporation load, which depends on the water and air temperatures and how busy the pool is as well as its area.
Ranges across the eight Techno-Pool models. Per-model data is in the technical catalogue.
03Specifications
04Model data
As published in the Techno-Pool technical catalogue.
A first guide from the catalogue figures. Our engineers confirm the selection for your project.
| Model | Pool surfacem² | Dehumidificationkg/h | Airflowm³/h | Cooling capacitykW | Heating capacitykW | Compressor circuits | Total powerkW | Dimensions (L × W × H)mm | Weightkg |
|---|---|---|---|---|---|---|---|---|---|
| TP-33 | 64 | 18.6 | 3,350 | 21.1 | 37.4 | 1 | 10.04 | 4,725 × 915 × 1,584 | 1,350 |
| TP-45 | 89 | 26.5 | 4,500 | 30.7 | 49.6 | 1 | 14.32 | 4,775 × 915 × 1,890 | 1,500 |
| TP-65 | 122 | 35.6 | 6,500 | 40.2 | 64.1 | 1 | 18.32 | 4,878 × 1,221 × 1,890 | 1,700 |
| TP-84 | 165 | 47.7 | 8,400 | 54.5 | 84.3 | 1 | 24.8 | 4,997 × 1,374 × 2,196 | 2,000 |
| TP-125 | 245 | 74.2 | 12,500 | 83 | 129.3 | 1 | 34.6 | 5,053 × 1,833 × 2,196 | 2,500 |
| TP-155 | 306 | 99.2 | 15,500 | 110.4 | 159.3 | 2 | 55.6 | 5,781 × 1,833 × 2,052 | 2,900 |
| TP-215 | 425 | 127.7 | 21,500 | 72.1 × 2 | 229.7 | 2 | 80.12 | 6,017 × 2,292 × 2,808 | 3,850 |
| TP-255 | 505 | 150.5 | 25,500 | 82.7 × 2 | 266.5 | 2 | 80.12 | 6,538 × 2,292 × 3,114 | 4,800 |
Full model codes end in -PHR-APF-NR-WH (e.g. TP-33-PHR-APF-NR-WH). Scroll compressors, R407C. Two plug fans, 350 Pa external pressure on return and supply, G4/G4 filters, fan motors 3P/380 V/50 Hz. Two-circuit models show cooling capacity per circuit (× 2). The catalogue does not state rating conditions for the capacities.
05Downloads
Tell us the airflow, the application and any space limits. We will size the Techno-Pool unit and send the performance data.