Designed & manufactured in İzmir, Türkiye

Language
info@technogen-hvac.com +90 532 201 00 11 Request a quote

Techno-Pool

Dehumidification and climate control for indoor swimming pools.

Technogen Techno-Pool, Pool Air Handling Units
  • 8models
  • 64–505m²pool surface area
  • 150.5kg/hmax. dehumidification
  • 25,500m³/hmax. airflow

01Overview

Sized to VDI 2089
for pools from 64 to 505 m².

Techno-Pool units control humidity and temperature in indoor pool halls: hotels, spa centres, municipal pools and private residences. Each unit is selected from the evaporation load, which VDI 2089 Part 1 calculates from the water area, the water and air temperatures and how the pool is used.

Every unit has heat recovery and a factory-mounted control panel, so it is ready to run when it arrives on site.

Heat recovery

Heat recovery as standard

All units are equipped with heat recovery systems that enhance energy efficiency.

R407C

Scroll compressors

R407C refrigerant with scroll compressors in single or dual circuits.

3 options

Fan choice

Belt-driven, plug fan or EC plug fan options.

G4 → F9

Filtration

Standard G4 panel filter with optional M5–F9 bag filters.

Epoxy

Corrosion-ready build

50 mm rock-wool insulation, epoxy-coated coils and a stainless-steel drainage system.

200 m

Smart automation

Humidity and temperature sensors, frequency converters, scheduling and remote control up to 200 m.

02Range

Eight models,
18.6 to 150.5 kg/h.

Techno-Pool covers pool surface areas from 64 to 505 m². Choose the model by evaporation load, which depends on the water and air temperatures and how busy the pool is as well as its area.

Pool surface area64 – 505 m²
0600
Dehumidification capacity18.6 – 150.5 kg/h
0175
Airflow≈ 1,972–15,009 CFM3,350 – 25,500 m³/h
030,000
Heating capacityUp to 266.5 kW
0300
Cooling capacityUp to 2 × 82.7 kW
0200

Ranges across the eight Techno-Pool models. Per-model data is in the technical catalogue.

03Specifications

Technical overview.

Models
8
Pool surface area
64 – 505 m²
Dehumidification
18.6 – 150.5 kg/h
Airflow
3,350 – 25,500 m³/h (≈ 1,970–15,010 CFM)
Cooling capacity
Up to 2 × 82.7 kW
Heating capacity
Up to 266.5 kW
Fans
Belt-driven, plug fan or EC plug fan
Refrigerant
R407C, scroll compressor (single or dual circuit)
Filtration
G4 panel filter standard; optional M5–F9 bag filters
Construction
50 mm rock-wool insulation, epoxy-coated coils, stainless-steel drainage
Automation
Humidity and temperature sensors, frequency converters, programmable scheduling, remote control up to 200 m
Applications
Hotels, spa centres, municipal facilities, luxury residences

04Model data

Figures from
the catalogue.

As published in the Techno-Pool technical catalogue.

m²

A first guide from the catalogue figures. Our engineers confirm the selection for your project.

ModelPool surfacem²Dehumidificationkg/hAirflowm³/hCooling capacitykWHeating capacitykWCompressor circuitsTotal powerkWDimensions (L × W × H)mmWeightkg
TP-336418.63,35021.137.4110.044,725 × 915 × 1,5841,350
TP-458926.54,50030.749.6114.324,775 × 915 × 1,8901,500
TP-6512235.66,50040.264.1118.324,878 × 1,221 × 1,8901,700
TP-8416547.78,40054.584.3124.84,997 × 1,374 × 2,1962,000
TP-12524574.212,50083129.3134.65,053 × 1,833 × 2,1962,500
TP-15530699.215,500110.4159.3255.65,781 × 1,833 × 2,0522,900
TP-215425127.721,50072.1 × 2229.7280.126,017 × 2,292 × 2,8083,850
TP-255505150.525,50082.7 × 2266.5280.126,538 × 2,292 × 3,1144,800

Full model codes end in -PHR-APF-NR-WH (e.g. TP-33-PHR-APF-NR-WH). Scroll compressors, R407C. Two plug fans, 350 Pa external pressure on return and supply, G4/G4 filters, fan motors 3P/380 V/50 Hz. Two-circuit models show cooling capacity per circuit (× 2). The catalogue does not state rating conditions for the capacities.

Download catalogue →

Send us
your drawings.

Tell us the airflow, the application and any space limits. We will size the Techno-Pool unit and send the performance data.