Zenair

Fan coil units in five model types, 2-pipe and 4-pipe.

Technogen Zenair, Fan Coil Units
  • 5model types
  • 2 & 4pipe versions
  • ECmotor options
  • 4international test standards

01Overview

Five fan coil formats,
1.4 to 13.6 kW cooling.

Zenair TF fan coils come in five types: ceiling concealed (PVA), cabinet ceiling (PCA), floor without cabinet (XVA) and two cabinet floor types (XCA-F and XCA-W). Each type is made in 2-pipe and 4-pipe versions, with left- or right-hand water connections. Cooling capacity runs from 1.4 to 13.6 kW at the catalogue’s rating conditions.

Sound pressure starts at 33 dB(A) at 1 m, at high speed, on the smallest floor and cabinet unit with an EC motor. The series has a Eurovent-certified design and a wide range of accessories.

Technogen Zenair TF-XCA-F cabinet floor fan coil unit under the window of a Paris hotel suite, standing against the panelled wall below the sill, drawing room air in underneath and supplying it through the top grille
In applicationZenair TF-XCA-F cabinet floor unit in a Paris hotel suite: room air drawn in underneath, conditioned air out through the top grille, pipes hidden in the wall.
1.4–13.6 kW

Cooling range

Total cooling from 1.4 to 13.6 kW (room 27 °C DB / 50% RH, water 7/12 °C).

33 dB(A)

Low noise near living areas

From 33 dB(A) at 1 m at high speed, on the smallest floor and cabinet EC unit.

30 W

Low energy use

EC motor versions: the smallest concealed unit draws 30 W at 504 m³/h.

2 & 4 pipe

Two- or four-pipe

Every model is available in 2-pipe and 4-pipe system versions.

238 mm

Slim concealed units

Concealed ceiling units are 238 mm high, for shallow ceiling voids.

70 Pa

Ducted versions

Concealed units deliver up to 60 Pa external static pressure with AC motors and 70 Pa with EC motors.

Tested to international standards

EN
1397

EN 1397

Heat exchangers: testing of water fan coil units.

ASHRAE
79

ANSI/ASHRAE 79

Methods of testing fan coil units.

AHRI
440

ANSI/AHRI 440

Performance rating of room fan coils.

AMCA
210

ANSI/AMCA 210

Laboratory methods for testing fans.

02Model types

Five formats,
2-pipe or 4-pipe.

Choose the type that suits the space. Every Zenair TF type is made in 2-pipe and 4-pipe versions, with left- or right-hand connections.

TF-PVA

Ceiling concealed

Hidden above a false ceiling and ducted to diffusers. Room air enters at the rear and conditioned air leaves at the front, at up to 60 Pa external static pressure with AC motors and 70 Pa with EC motors.

At a glance
  • Above the ceiling
  • Ducted

03Specifications

Technical overview.

Model types
TF-PVA ceiling concealed, TF-PCA cabinet ceiling, TF-XVA floor without cabinet, TF-XCA-F cabinet floor (bottom inlet), TF-XCA-W cabinet floor (front inlet)
Systems
2-pipe and 4-pipe versions
Connections
Left- or right-hand water connections
Motors
Energy-efficient EC motor options
Certification
Eurovent-certified design
Testing
EN 1397, ANSI/ASHRAE 79, ANSI/AHRI 440, ANSI/AMCA 210
Acoustics
From 33 dB(A) at 1 m, high speed (smallest floor and cabinet EC unit)
Accessories
Wide range of models and accessories
Delivery & service
Fast delivery from stock, extensive service network

04Model data

Figures from
the catalogue.

As published in the Zenair technical catalogue.

Concealed ceiling

2-pipe

ModelTotal cooling capacitykWSensible cooling capacitykWHeating capacitykWAirflow (high speed)m³/hWater flow (cooling)l/hWater pressure drop (cooling)kPaSound pressure (high speed)dB(A)Power input (high speed)WDimensions (W × H × D)mm
0151.921.533.864473385.83847709 × 238 × 478
0202.561.814.47430446.714.23846709 × 238 × 478
0252.952.085.15483515.318.64461709 × 238 × 478
0303.792.87.02792662274476984 × 238 × 478
0354.783.48.43836833.320.64483984 × 238 × 478
0405.263.729.17876917.124.34590984 × 238 × 478
0505.944.1210.079361,033.534.244921,101 × 238 × 478
0606.974.8311.851,1091,216449.1481211,024 × 238 × 478
0708.025.613.91,3001,400.334.3471501,359 × 238 × 478
0808.946.2615.61,4741,563.443.1481761,411 × 238 × 478
10010.657.5319.681,7691,856.527.9471781,771 × 238 × 478
11012.458.79232,0972,174.539492331,882 × 238 × 478

TF-PVA, version 2A (AC motor, up to 60 Pa ESP). Capacities at high speed. Cooling: room 27 °C DB / 50% RH, water 7/12 °C. Heating: room 20 °C DB, water 70/50 °C. 0 Pa external static pressure. Sound pressure at 1 m (Q = 1).

4-pipe

ModelTotal cooling capacitykWSensible cooling capacitykWHeating coil capacitykWAirflow (high speed)m³/hWater flow (cooling)l/hWater pressure drop (cooling)kPaWater flow (heating)l/hWater pressure drop (heating)kPaSound pressure (high speed)dB(A)Power input (high speed)WDimensions (W × H × D)mm
0151.821.442.8417320.25.41212.43846709 × 238 × 478
0202.451.722.53407427.513.5108.923845709 × 238 × 478
0252.771.962.96448484.617.3126.32.64459709 × 238 × 478
0303.562.625.03727623.725217.69.54476984 × 238 × 478
0354.533.214.84783790.819.2208.98.84480984 × 238 × 478
0404.913.465.38806856.122.2232.510.74585984 × 238 × 478
0505.63.876.1872975.431.5263.91544881,101 × 238 × 478
0606.634.587.121,0431,156.945.8307.421.3471141,024 × 238 × 478
0707.495.217.831,1961,308.830.9337.24.7441451,359 × 238 × 478
0808.365.828.671,3571,461.238.8372.95.8481671,411 × 238 × 478
1009.987.0210.951,6321,741.124.9472.910.6471721,771 × 238 × 478
11011.728.2412.691,9432,046.835.4546.914.5492171,882 × 238 × 478

TF-PVA, version 4A (AC motor, up to 60 Pa ESP), with a separate heating coil. Capacities at high speed. Cooling: room 27 °C DB / 50% RH, water 7/12 °C. Heating coil: room 20 °C DB, water 70/50 °C. 0 Pa external static pressure. Sound pressure at 1 m (Q = 1).

Concealed ceiling · EC

2-pipe

ModelTotal cooling capacitykWSensible cooling capacitykWHeating capacitykWAirflow (turbo speed)m³/hWater flow (cooling)l/hWater pressure drop (cooling)kPaSound pressure (high speed)dB(A)Power input (turbo speed)WDimensions (W × H × D)mm
0152.041.644.08504354.46.23830709 × 238 × 478
0253.412.466.01597593.623.64452709 × 238 × 478
0304.213.167.84963733.731.64463984 × 238 × 478
0405.864.2210.351,0421,021.528.84594984 × 238 × 478
0506.54.5711.061,0681,129.738.744881,101 × 238 × 478
0607.695.3913.171,2851,342.656.4471351,024 × 238 × 478
0708.756.2115.161,4811,522.438.1441221,101 × 238 × 478
0809.86.9617.131,7021,710.448.6481641,024 × 238 × 478
10011.418.1920.941,9731,986.730.1471641,411 × 238 × 478
11013.629.7525.22,4302,383.244492671,882 × 238 × 478

TF-PVA, version 2M (EC motor, up to 70 Pa ESP). Capacities at turbo speed. Cooling: room 27 °C DB / 50% RH, water 7/12 °C. Heating: room 20 °C DB, water 70/50 °C. 0 Pa external static pressure. Sound pressure at 1 m (Q = 1).

4-pipe

ModelTotal cooling capacitykWSensible cooling capacitykWHeating coil capacitykWAirflow (turbo speed)m³/hWater flow (cooling)l/hWater pressure drop (cooling)kPaWater flow (heating)l/hWater pressure drop (heating)kPaSound pressure (high speed)dB(A)Power input (turbo speed)WDimensions (W × H × D)mm
0151.921.542.43462334.25.6105.723928709 × 238 × 478
0253.242.332.74554563.821.5118.42.44448709 × 238 × 478
0303.922.924.55860682.627.7197.78.34458984 × 238 × 478
0405.483.934.85945955.625.5209.59.24585984 × 238 × 478
0506.124.295.369801,063.234.623212.444811,101 × 238 × 478
0607.295.096.341,1901,27351.227317.8471251,024 × 238 × 478
0708.195.786.861,3461,424.333.8296.43.8441121,359 × 238 × 478
0809.226.527.691,5561,608.643.4331.14.8491501,411 × 238 × 478
10010.687.619.481,7921,857.726.6409.88.5471501,771 × 238 × 478
11012.839.1411.292,2252,243.939.4485.312.2492461,882 × 238 × 478

TF-PVA, version 4M (EC motor, up to 70 Pa ESP), with a separate heating coil. Capacities at turbo speed. Cooling: room 27 °C DB / 50% RH, water 7/12 °C. Heating coil: room 20 °C DB, water 70/50 °C. 0 Pa external static pressure. Sound pressure at 1 m (Q = 1).

Floor & cabinet ceiling

2-pipe

ModelTotal cooling capacitykWHeating capacitykWAirflow (high speed)m³/hWater flow (cooling)l/hWater pressure drop (cooling)kPaSound pressure (high speed)dB(A)Power input (high speed)WXCA dimensions (W × H × D)mmXVA dimensions (W × H × D)mm
0151.512.96335264.34.43432850 × 545 × 231647 × 513 × 221
0202.043.39310354.611.23531850 × 545 × 231647 × 513 × 221
0252.684.65449469.718.84259850 × 545 × 231647 × 513 × 221
0303.295.96675574.525.138581,110 × 545 × 231907 × 513 × 221
0354.026.73632698.217.736571,110 × 545 × 231907 × 513 × 221
0404.667.97773812.423.243761,110 × 545 × 231907 × 513 × 221
0505.428.68789941.138.240731,370 × 545 × 2311,167 × 513 × 221
0606.3711.31,1131,112.314.5461161,370 × 545 × 2311,167 × 513 × 221
0707.3412.371,1511,277.722.1461151,630 × 545 × 2311,167 × 513 × 221
0808.2514.121,3491,438.427.5481451,630 × 545 × 2311,167 × 513 × 221
1009.415.521,4371,636.339.7461421,890 × 545 × 2311,687 × 513 × 221
11010.8818.331,7511,849.951.9481721,890 × 545 × 2311,687 × 513 × 221

TF-PCA, XVA and XCA share one table. Version 2C (AC motor, up to 60 Pa ESP). Capacities at high speed. The catalogue gives dimensions for XCA and XVA only. Cooling: room 27 °C DB / 50% RH, water 7/12 °C. Heating: room 20 °C DB, water 70/50 °C. 0 Pa external static pressure. Sound pressure at 1 m (Q = 1).

4-pipe

ModelTotal cooling capacitykWHeating coil capacitykWAirflow (high speed)m³/hWater flow (cooling)l/hWater pressure drop (cooling)kPaWater flow (heating)l/hWater pressure drop (heating)kPaSound pressure (high speed)dB(A)Power input (high speed)WXCA dimensions (W × H × D)mmXVA dimensions (W × H × D)mm
0151.421.66309248.83.971.80.93531850 × 545 × 231647 × 513 × 221
0201.921.59288335.19.968.60.93630850 × 545 × 231647 × 513 × 221
0252.542.03417444.316.986.81.44457850 × 545 × 231647 × 513 × 221
0303.143.3562554722.8145.14.741571,110 × 545 × 231907 × 513 × 221
0353.813.24589662.3161404.447561,110 × 545 × 231907 × 513 × 221
0404.383.66711763.320.71585.544731,110 × 545 × 231907 × 513 × 221
0505.174.37745898.435.1189.39.641721,370 × 545 × 2311,167 × 513 × 221
0606.115.431,0511,065.713.5234.314.3481111,370 × 545 × 2311,167 × 513 × 221
0706.975.791,0761,214.520.1249.73.2471131,630 × 545 × 2311,167 × 513 × 221
0807.816.391,2541,363.424.8275.13.8491411,630 × 545 × 2311,167 × 513 × 221
1008.885.391,3361,546.735.9232.912.8441401,890 × 545 × 2311,687 × 513 × 221
11010.268.231,6181,787.346.5355.26.9471641,890 × 545 × 2311,687 × 513 × 221

TF-PCA, XVA and XCA share one table. Version 4C (AC motor, up to 60 Pa ESP), with a separate heating coil. Capacities at high speed. The catalogue gives dimensions for XCA and XVA only. Cooling: room 27 °C DB / 50% RH, water 7/12 °C. Heating coil: room 20 °C DB, water 70/50 °C. 0 Pa external static pressure. Sound pressure at 1 m (Q = 1).

Floor & cabinet ceiling · EC

2-pipe

ModelTotal cooling capacitykWHeating capacitykWAirflow (high speed)m³/hWater flow (cooling)l/hWater pressure drop (cooling)kPaSound pressure (high speed)dB(A)Power input (high speed)WXCA dimensions (W × H × D)mmXVA dimensions (W × H × D)mm
0151.733.28329300.25.23314850 × 545 × 231647 × 513 × 221
0253.215.45440557.824.24130850 × 545 × 231647 × 513 × 221
0303.616.33646625.327.237301,110 × 545 × 231907 × 513 × 221
0405.258.81747912.826.942531,110 × 545 × 231907 × 513 × 221
0506.039.417611,042.342.739401,370 × 545 × 2311,167 × 513 × 221
0607.2112.611,0841,258.116.945941,370 × 545 × 2311,167 × 513 × 221
0809.2715.521,3131,611.731.147971,630 × 545 × 2311,167 × 513 × 221
11012.2320.231,7232,127.758.9471381,890 × 545 × 2311,687 × 513 × 221

TF-PCA, XVA and XCA share one table. Version 2E (EC motor, up to 70 Pa ESP). Capacities at high speed. The catalogue gives dimensions for XCA and XVA only. Cooling: room 27 °C DB / 50% RH, water 7/12 °C. Heating: room 20 °C DB, water 70/50 °C. 0 Pa external static pressure. Sound pressure at 1 m (Q = 1).

4-pipe

ModelTotal cooling capacitykWHeating coil capacitykWAirflow (high speed)m³/hWater flow (cooling)l/hWater pressure drop (cooling)kPaWater flow (heating)l/hWater pressure drop (heating)kPaSound pressure (high speed)dB(A)Power input (high speed)WXCA dimensions (W × H × D)mmXVA dimensions (W × H × D)mm
0151.581.78289274.64.477.413419850 × 545 × 231647 × 513 × 221
0252.982.27394517.321981.64331850 × 545 × 231647 × 513 × 221
0303.233.37540560.622.3146.54.540281,110 × 545 × 231907 × 513 × 221
0404.783.88655831.222.6167.95.743531,110 × 545 × 231907 × 513 × 221
0505.554.55682960.636.8197.99.640411,370 × 545 × 2311,167 × 513 × 221
0606.745.879861,176.114.9252.91547891,370 × 545 × 2311,167 × 513 × 221
0808.566.781,1741,487.626.8293.43.948911,630 × 545 × 2311,167 × 513 × 221
11011.258.81,5301,955.450.5379.97.1461291,890 × 545 × 2311,687 × 513 × 221

TF-PCA, XVA and XCA share one table. Version 4E (EC motor, up to 70 Pa ESP), with a separate heating coil. Capacities at high speed. The catalogue gives dimensions for XCA and XVA only. Cooling: room 27 °C DB / 50% RH, water 7/12 °C. Heating coil: room 20 °C DB, water 70/50 °C. 0 Pa external static pressure. Sound pressure at 1 m (Q = 1).

Download catalogue →

Send us
your drawings.

Tell us the airflow, the application and any space limits. We will size the Zenair unit and send the performance data.