Designed & manufactured in İzmir, Türkiye

Language
info@technogen-hvac.com +90 532 201 00 11 Request a quote
Heat recovery family
SuperairZephyrSenseAir

Superair

Ceiling-type heat recovery units with Eurovent-certified plate heat exchangers.

Technogen Superair, Heat Recovery Units
  • 9airflow models
  • 800–6,000m³/hairflow range
  • 25mmdouble-skin insulation
  • 230Vsingle-phase supply

01Overview

Ceiling-mounted heat recovery
for offices, hotels and restaurants.

Superair units extract stale air, supply fresh air and pass heat between the two airstreams through a Eurovent-certified cross-flow plate exchanger.

They suit offices, hotels, restaurants, hospitals, cinemas, exhibition halls and residential buildings.

Eurovent

Certified heat exchangers

Every Superair heat exchanger is a Eurovent-certified cross-flow plate.

Plug fans

Low-noise plug fans

Backward-curved plug fans on directly coupled AC motors for low energy use and low noise.

25 mm

Double-skin insulation

25 mm flame-retardant double-skin insulation throughout the casing.

G4 · M5

Two-stage filtration

G4 filters in both fresh-air and exhaust streams, with ePM10 50% (M5) class filters.

3 options

Configurable options

Electric heaters, hot-water coils and silencers adapt each unit to the project.

BMS

Controls & BMS

Optional digital room control panels and integration with building management systems.

02How it works

Separate channels
for supply and extract.

Superair recovers heat from exhaust air through a cross-flow plate exchanger, so fresh air arrives pre-tempered.

  1. 01

    Extract

    Stale air is drawn from the space and passes through the plate exchanger.

  2. 02

    Exchange

    Heat passes through the thin plates. The two airstreams stay in separate channels.

  3. 03

    Supply

    Filtered fresh air enters the space already pre-tempered.

03Range

Nine models,
800 to 6,000 m³/h.

Nine airflow models cover 800 to 6,000 m³/h. Pick by airflow, then check the fan curve against your duct pressure.

Airflow≈ 471–3,531 CFM800 – 6,000 m³/h
TEVHR-800 · 865 m³/h · 57 dB(A)TEVHR-6000 · 6,000 m³/h · 59 dB(A)
07,000
Fan motor power270 – 1,600 W
02,000

Ranges across the nine Superair models. Data for every model is in the technical catalogue.

04Specifications

Technical overview.

Type
Ceiling-type heat recovery unit
Models
9 airflow capacity models
Airflow
800 – 6,000 m³/h (≈ 470–3,530 CFM)
Heat exchanger
Eurovent-certified cross-flow plate
Fans
Backward-curved plug fans, directly coupled AC motors
Fan motor power
270 – 1,600 W
Noise
57 dB(A) (TEVHR-800) · 59 dB(A) (TEVHR-6000)
Insulation
25 mm flame-retardant double-skin
Filtration
G4 in fresh-air and exhaust streams · ePM10 50% (M5)
Options
Electric heater, hot-water coil, silencer
Controls
Optional digital room control panel, BMS integration
Electrical
230 V / 50 Hz, single-phase
Service
User-friendly service doors, modular structure

05Model data

Figures from
the catalogue.

As published in the Superair technical catalogue.

Performance

ModelAirflowm³/hSound leveldB(A)Fan powerWMax. currentA
TEVHR-800865572701.2
TEVHR-10001,210593101.4
TEVHR-15001,500624502.0
TEVHR-20002,100504502.0
TEVHR-25003,150557503.5
TEVHR-30003,150557503.5
TEVHR-40004,400559404.8
TEVHR-50006,000551,3006.0
TEVHR-60006,000591,6008.0

Airflow and fan power at 0 Pa external static pressure. Sound level at 250 Hz, 1.5 m from the unit. Power supply 1~230 V 50 Hz. Every model comes with rectangular (R) or circular (C) duct connections; the figures are the same.

Dimensions

ModelWidthmmDepthmmHeightmmRectangular duct (R)mmCircular duct Ø (C)mmWeightkg
TEVHR-8006761,110315220 × 22020060
TEVHR-10008381,262374220 × 22020075
TEVHR-15008381,362424270 × 27025085
TEVHR-20009381,498474320 × 320300110
TEVHR-25001,0601,894544370 × 370355135
TEVHR-30001,0601,894544370 × 370355135
TEVHR-40001,2032,151633450 × 450400160
TEVHR-50001,2032,151633450 × 450450190
TEVHR-60001,2242,151672500 × 500500210

Width, depth and height are dimensions A, B and C of the catalogue drawing.

Download catalogue →

06Fan curves

Airflow
against pressure.

Redrawn from the curves in the Superair technical catalogue. Move along a curve to read it.

010020030040002004006008001,000 Airflow (m³/h) Pressure (Pa)
020040060005001,0001,500 Airflow (m³/h) Pressure (Pa)
020040060080005001,0001,500 Airflow (m³/h) Pressure (Pa)
020040060005001,0001,5002,0002,500 Airflow (m³/h) Pressure (Pa)
010020030040050001,0002,0003,000 Airflow (m³/h) Pressure (Pa)
010020030040050001,0002,0003,0004,000 Airflow (m³/h) Pressure (Pa)
010020030040050001,0002,0003,0004,000 Airflow (m³/h) Pressure (Pa)
020040060001,0002,0003,0004,0005,000 Airflow (m³/h) Pressure (Pa)
020040060080002,0004,0006,000 Airflow (m³/h) Pressure (Pa)

Redrawn from the fan curves on pages 8–25 of the SuperAir technical catalogue. The R (rectangular duct) and C (circular duct) versions of each model share the same curve.

Send us
your drawings.

Tell us the airflow, the application and any space limits. We will size the Superair unit and send the performance data.