Designed & manufactured in İzmir, Türkiye

Language
info@technogen-hvac.com +90 532 201 00 11 Request a quote
Heat recovery family

Zephyr

Room ventilation with heat recovery for spaces without existing ventilation infrastructure.

  • 90%thermal efficiency, up to
  • 70sregenerative cycle
  • Wi-Fimulti-unit sync
  • 0.9Win night mode
Technogen Zephyr, Heat Recovery Units

01Overview

Fresh air, without
the ductwork.

Zephyr ventilates a single room through the wall, in buildings with no ventilation ductwork. At full speed it moves 60 m³/h on 5.9 W.

A reversing fan and a ceramic heat exchanger let it recover heat while it ventilates. Several units can run in sync over Wi-Fi.

Ceramic

Ceramic heat exchanger

A high-efficiency ceramic core stores heat from outgoing air and returns it to incoming air.

Dual-flow

Dual-flow fan technology

The fan reverses direction every half-cycle to alternate extract and supply.

90%

Up to 90% efficiency

Up to 90% thermal efficiency for comfortable air at low energy cost.

0.9 W

Low consumption

0.9 W in night mode, 5.9 W at full speed (60 m³/h).

Wi-Fi

Synchronised units

Multiple units connect over Wi-Fi to run in sync for larger spaces.

−25 °C

Year-round operation

Operating range −25 to +40 °C, with an IPX4-rated enclosure.

02How it works

A 70-second cycle
that keeps the heat in.

Zephyr alternates airflow direction. The ceramic core charges with heat on the way out and releases it on the way in.

One full cycle takes 70 seconds. The animation runs faster.

03Specifications

Technical overview.

Type
Room ventilation unit with heat recovery
Heat exchanger
High-efficiency ceramic, regenerative
Operating cycle
70 seconds, alternating airflow direction
Thermal efficiency
Up to 90%
Fan
Dual-flow fan technology
Power consumption
0.9–5.9 W
Connectivity
Built-in wireless; multiple units sync over Wi-Fi
Application
Spaces without existing ventilation infrastructure

04Model data

Figures from
the catalogue.

As published in the Zephyr technical catalogue.

Fan speedAirflowm³/hPowerWSound powerSound pressure at 1 mdB(A)Sound pressure at 3 mdB(A)
Night mode150.921.310.30.8
I301.125.714.75.1
II452.839.828.819.2
III605.947.936.927.3

Sound power is printed without a unit. Measured with the standard G3 filter; the optional M5 filter can change airflow and noise. 110/230 V 50/60 Hz, IPX4, operating temperature −25 to +40 °C.

Download catalogue →

Send us
your drawings.

Tell us the airflow, the application and any space limits. We will size the Zephyr unit and send the performance data.