Language
info@technogen-hvac.com +90 532 201 00 11 Request a quote
Heat recovery family
SuperairCOREZephyrSenseAir

CORE

Double-skin heat recovery units with a Eurovent-certified counter-flow heat exchanger and EC fans.

Technogen CORE, Heat Recovery Units
  • 5airflow models
  • 500–3,000m³/hairflow range
  • 79.7%max. EN 308 efficiency
  • 50mmrock-wool side panels

01Overview

Counter-flow heat recovery
in a double-skin casing.

CORE units supply filtered fresh air and extract stale air, passing heat between the two airstreams through an aluminium counter-flow heat exchanger that is Eurovent-certified and complies with EN 308.

Five models cover 500 to 3,000 m³/h, with EC fans, a front electric heater and a choice of Basic or Professional control cards with Modbus-RTU.

Technogen CORE counter-flow heat recovery unit seen from below, hung from a concrete slab, with four round duct connections: insulated outside-air and exhaust ducts at one end entering the external wall, galvanised supply and return ducts at the other
In applicationCORE under a concrete slab, seen from below: outside-air and exhaust ducts at the outdoor end, supply and return ducts at the room end, with the two airstreams in opposite directions.
Eurovent

Counter-flow heat exchanger

An aluminium counter-flow exchanger, Eurovent-certified and compliant with EN 308, up to 79.7% efficiency.

EC

EC fans

Backward-curved fans on EC motors, with five-stage speed control and a low specific fan power.

50 mm

Double-skin casing

0.8 mm galvanised inner and painted outer skins, 50 mm rock-wool side panels and 30 mm top, bottom and service panels.

F8 · M5

Supply and extract filters

M6 + F8 (or G4 + F9) on the supply and M5 on the extract, with filter monitoring on the control panel.

Bypass

Free cooling

A bypass damper lets outdoor air skip the heat exchanger when free cooling is possible.

Modbus

Two control cards

Basic or Professional control card with Modbus-RTU. Professional adds constant airflow, CO₂ control and an electric reheater.

02How it works

Two airstreams,
one counter-flow core.

Stale and fresh air pass each other in opposite directions through the aluminium exchanger, so the fresh air arrives tempered.

  1. 01

    Extract

    Stale air is filtered through the M5 extract filter and drawn into the exchanger.

  2. 02

    Exchange

    Heat passes through the aluminium plates of the counter-flow core. The two airstreams never mix.

  3. 03

    Supply

    Fresh air is filtered to F8 (or F9) and enters the space already tempered.

03Range

Five models,
500 to 3,000 m³/h.

Choose by nominal airflow, then check the model’s performance curve against your duct pressure in the catalogue.

Nominal airflow≈ 271–1,766 CFM460 – 3,000 m³/h
CR-T500 · 460 m³/hCR-T3000 · 3,000 m³/h
03,500
Heat recovery efficiency (EN 308)78.5 – 79.7 %
0100
Fan power174 – 756 W
01,000

Ranges across the five CORE models. Curves and dimensions for every model are in the technical catalogue.

04Specifications

Technical overview.

Type
Double-skin heat recovery unit
Models
5 models: CR-T500, CR-T1000, CR-T1500, CR-T2300, CR-T3000
Airflow
460 – 3,000 m³/h nominal (≈ 270–1,770 CFM)
Heat exchanger
Aluminium counter-flow, Eurovent-certified, EN 308
Fans
Backward-curved, EC motors, 5-stage speed control
Casing
0.8 mm galvanised inner skin, 0.8 mm painted outer skin
Insulation
Rock wool, 70 kg/m³: 50 mm side panels, 30 mm top, bottom and service panels
Filtration
Supply M6 + F8 (or G4 + F9) · extract M5
Heating
Front electric heater with thermistor and stepped control
Controls
Basic or Professional control card, Modbus-RTU
Operating temperature
−20 to 50 °C
Protection class
IP 31
Electrical
230 V / 50 Hz, single-phase

05Model data

Figures from
the catalogue.

As published in the CORE technical catalogue.

ModelNominal airflowm³/hMax. airflow (0 Pa)m³/hMin. airflowm³/hEfficiency (EN 308)%Sound power LwAdB(A)Fan powerWCurrentAWeightkg
CR-T50046055013078.538.51741.4110
CR-T10009501,05016079.041.52601.74160
CR-T15001,4501,40017579.146.55402.4210
CR-T23002,2002,30025079.747.06402.9280
CR-T30003,0003,15031079.144.07565.6320

Fan power and current are for both fans together. Sound power is the total airborne level at nominal airflow. Power supply 1~230 V 50 Hz. Performance curves and dimension drawings are in the catalogue.

Download catalogue →

Send us
your drawings.

Tell us the airflow, the application and any space limits. We will size the CORE unit and send the performance data.